Wall Mount

By code, all transformers must be installed a minimum of 12" above finish grade as measured from finish grade to the bottom of the transformer. Using the template enclosed within the accessories bag and a 9" torpedo level, mark top anchor locations on wall, drill pilot holes, insert anchors and install screws into anchors leaving approximately 1/8" of thread exposed on the screw. Mount transformer on screws.

Mark locations for bottom anchors with permanent marker. Remove transformer from wall. Drill bottom anchor holes, install anchors. Place transformer back on top anchors and install screw(s) into anchors at bottom of transformer to secure it to the wall.

A - Side View
B - Front View

  1. 1½" conduit
  2. 120 volt receptacle with weatherproof cover
  3. Power cord
  4. 12" minimum
  5. Mounting brackets
Post Mount Installation

Install pressure treated 4" x 4" x 36" (min) post in concrete footing. Install single anchor screw (provided) 1½"–2" below the top of post. Place transformer on screw. Place a 9" torpedo level on top of transformer and level transformer. Once level, secure transformer to post by installing 1 or 2 screws on the bottom mounting bracket.

A - Side View
B - Front View

  1. 1½" conduit
  2. 4 x 4 post
  3. Concrete footing
  4. 12" minimum
  5. Mounting brackets